Description
UPS XT series 100kva-300kva Tescom
Tikweld Welding Supplies and Services is a distributor of Tescom Power Products in Nigeria. The UPS XT series 100kva-300kva are true online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.
Features of UPS XT series 100kva-300kva Tescom
- Output isolation transformer
- Up to 91% efficiency
- Static by-pass
- LCD front panel
- 128 events alarm memory (4000 alarms)
- RS232 and relay contacts
- Custom input and output voltage ranges
- SNMP compatible communication
- T-MON remote monitoring software
- Parallel operation up to 4 devices
- High performance at nonlinear loads
- Custom input voltage and frequency ranges
Specification of UPS XT series 100kva-300kva Tescom
MODEL |
3100 |
3120 |
3160 |
3200 |
3250 |
3300 |
Power (kVA) |
100 |
120 |
160 |
200 |
250 |
300 |
INPUT |
||||||
Voltage |
380/400 VAC 3P + N + G ± 15% |
|||||
By-pass voltage |
380/400 VAC 3P + N ± 10% |
|||||
Input frequency |
50Hz (60Hz on request) ± 5% |
|||||
OUTPUT |
||||||
Power (kW) |
80 |
96 |
128 |
160 |
200 |
240 |
Power factor |
0,8 |
|||||
Voltage |
380/400 VAC 3P + N |
|||||
Voltage stability |
Balanced load: ± 1%, Unbalanced load: ± 2%, Step load: ± 5% |
|||||
Voltage recovery time |
After step load: max. 25ms |
|||||
Frequency |
50Hz (60Hz on request) |
|||||
Frequency tolerance |
Line synchronized: ± 2% , free running: ± 0,2% |
|||||
Efficiency (at 100% load) |
90-92% |
|||||
Crest factor |
3:1 |
|||||
Overload protection |
100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass |
|||||
Short circuit protection |
Electronic short circuit protection |
|||||
Voltage THD |
Linear load: < 3% |
|||||
Non linear load: < 5% |
||||||
BATTERIES |
||||||
Type |
Sealed Lead Acid - Maintenance Free |
|||||
Number of batteries |
30 |
32 |
||||
Float charging voltage |
405 VDC |
432 VDC |
||||
End of discharge voltage |
300 VDC |
320 VDC |
||||
Battery ambient temperature |
25ºC |
|||||
Battery protection |
Automatic circuit breaker |
|||||
Battery test |
Automatic every 72 hours |
|||||
GENERAL |
||||||
Standards |
EN 62040-1,EN62040-2 |
|||||
Serial communication |
Dry contacts & RS232 |
|||||
Software |
T-Mon UPS Management Software (3 clients, +1 server management std.) |
|||||
Temperature range |
0ºC - 40ºC |
|||||
Ventilation |
Forced air cooling |
|||||
Relative humidity |
< %90 (non-condensing) |
|||||
Protection degree |
IP20 |
|||||
Altitude |
< 2000m above sea level |
|||||
Acoustic noise |
65 dBA |
70 dBA |
||||
Weight without batteries (kg) |
750 |
765 |
802 |
970 |
1328 |
1370 |
Dimensions (mm) HxWxD |
1650x1110x810 |
1730x1195x870 |
1880x1565x925 |
|||
OPTIONS |
||||||
Different input / output voltage |
Please ask |
|||||
Input transformer |
Galvanic isolation transformer at the input (in external cabinet) |
|||||
Input THD |
10% (with 12 Pulse or 18 Pulse rectifier, according to UPS range) |
|||||
5% (with 18 Pulse rectifier, + filter), up to 100kVA |
||||||
Input power factor |
0,95 - 0,98 (with 18 Pulse rectifier) |
|||||
Adaptors |
SNMP, MODBUS, Remote Mon. Panel, RS485 |
|||||
Parallel operation |
N + 1 (up to 4 units) |
|||||
(*): |
In 18Pulse & 12Pulse applications, the standard chassis dimensions may change. |
Contact us today for more info.
1 Review
-
Effective
Stepping into your firm for business transaction has been one of the best decision I have taken so far... I have purchased several UPS because that's basically what I deal on and have never had reasons to be discouraged. You see this UPS XT SERIES 100KVA-300KVA TESCOM, It is one of it's kind, It has great features like, Output isolation transformer, Up to 91% efficiency, Static by-pass etc and has served me so well. Thanks guys for always satisfying me.